SMC Networks HRS100-A?-20-? Operation Manual page 77

Thermo chiller
Hide thumbs Also See for HRS100-A?-20-?:
Table of Contents

Advertisement

Checking: Refrigerant circuit pressure on the low pressure side
6.
Press the [SEL] key once.
Display of the refrigerant circuit pressure on the low pressure side appears on the digital
display.
PV
SV
Checking: Accumulated operating time of the pump
7.
Press the [SEL] key once.
Display of the accumulated operating time of the pump appears on the digital display.
PV
SV
Refer to the table below for details of the display.
Accumulated time
1,000h to 99,999h
AL28 Pump maintenance alarm is generated when the accumulated operating time of the
pump reaches 20,000 hours (
"Chapter 6 Alarm Notification and Troubleshooting "
Checking: Accumulated operating time of the fan
8.
Press the [SEL] key once.
Display of the accumulated operating time of the fan appears on the digital display.
PV
SV
Refer to " Table 5.5-2 " for the display.
AL29 Fan maintenance alarm is generated when the accumulated operating time of
the fan motor reaches 30,000 hours (
refer to "Chapter 6 Alarm Notification and Troubleshooting ".
HRS Series
Table 5.5-2 Time display
0h to 999h
100,000h
Chapter 5
Display and setting of various functions
Displayed value
to
to
Return to
) (when set to "A.RUN"). For more details, refer to
.
) (when set to "A.RUN"). For details,
HRX-OM-S004
5.5Check monitor menu
5-11