SMC Networks HRS100-A?-20-? Operation Manual page 124

Thermo chiller
Hide thumbs Also See for HRS100-A?-20-?:
Table of Contents

Advertisement

HRX-OM-S004
Chapter 5
Display and setting of various functions
Setting/Checking: Operation setting when "Communication error" alarm is generated
20.
Press the [SEL] key once.
Operation setting screen when "Communication error" alarm is generated appears on
the digital display.
PV
SV
21.
Set operation when "Communication error" alarm is generated with [▲] key or [▼] key,
and press [SEL] key to enter.
Table 5.20-17 Operation setting when "Communication error" alarm is generated
Set value
Setting/Checking: Threshold monitoring time setting for "Communication error"
22.
Press the [SEL] key once.
Monitoring time setting screen for "Communication error" alarm appears on the digital
display.
PV
SV
23.
Set monitoring time for "Communication error" alarm with [▲] key or [▼] key, and press
[SEL] key to enter.
Table 5.20-18 Monitoring time for "Communication error" alarm setting
Set value
to
Setting/Checking: Operation setting when "Contact input 1 signal detection" alarm is generated
24.
Press the [SEL] key once.
Operation setting screen when "Contact input 1 signal detection" alarm is generated
appears on the digital display.
PV
SV
5.20 Alarm customizing function
5-58
Explanation
This alarm is not detected.
Operation continues when this alarm is
generated.
Operation stops when this alarm is generated.
Explanation
Setting/checking of the alarm is impossible
when the "AS11 Communication error" alarm
is set OFF.
Monitoring time for "Communication error" is
set.
Setting unit: 1 second
Initial value
(Default setting)
Initial value
(Default setting)
HRS Series