HRX-OM-S004
Chapter 5
Display and setting of various functions
29.
Set the product operation when "DC line fuse cut" alarm is generated with [▲] key or [▼]
key, and press [SEL] key to enter.
Table 5.20-21 Operation setting when "DC line fuse cut" alarm is generated
Set value
Setting/Checking: Temperature alarm monitoring method
30.
Press the [SEL] key once.
Setting screen of the temperature alarm monitoring method appears on the digital
display.
PV
SV
31.
Set temperature alarm monitoring method with [▲] key or [▼] key, and press [SEL] key
to enter.
Set value
Item
Continuous
monitoring
Automatic
monitoring
Monitoring
timer
Automatic
monitoring
Monitoring
timer
∗ Settings of this function and example of alarm generating timing for "5.20.3 Setting of temperature
alarm monitoring method and alarm generation timing ".
5.20 Alarm customizing function
5-60
Explanation
Operation continues when this alarm is
generated.
Operation stops when this alarm is generated.
Table 5.20-22 Setting of temperature alarm monitoring method
Alarm monitoring starts at the same time as
the product is turned ON. When the
ambient temperature is out of the range
between the temperatures set for AS.04 and
AS.06, AL.03 or AL.04 may be generated at
the same time when the product is turned
ON.
When the circulating fluid temperature is
outside of the alarm threshold range at the
time of operation start, the alarm will not be
generated until the temperature comes inside
the alarm threshold range.
Alarm will not be generated until it reaches
the time set for the AS.22 "Monitoring start
start
timer" after the operation starts.
Alarm monitoring starts when the set time has
passed.
Alarm will not be generated until it reaches
the time set for the AS.22 "Monitoring start
timer" after the operation starts.
Alarm monitoring starts when the set time has
+
passed.
start
When the circulating fluid temperature enters
the alarm threshold range before it reaches
the set time, the alarm monitoring will be
started at that time.
Explanation
Initial value
(Default setting)
Initial value
(Default setting)