SMC Networks HRS100-A?-20-? Operation Manual page 146

Thermo chiller
Hide thumbs Also See for HRS100-A?-20-?:
Table of Contents

Advertisement

HRX-OM-S004
Chapter 5
Display and setting of various functions
42.
Set time delay for the contact input signal 2 delay timer for reading with [▲] key or [▼]
key, and press [SEL] key to enter.
Table 5.21-22 Setting of time delay for the contact input signal 2 delay timer for reading
Set value
to
Setting/Checking: Contact input signal 2 OFF detection timer
43.
Press the [SEL] key once.
Setting screen of contact input signal 2 OFF detection timer is displayed on the digital
display.
PV
SV
44.
Set threshold time for the contact input signal 2 OFF detection timer with [▲] key or [▼]
key, and press [SEL] key to enter.
Table 5.21-23 Time setting for contact input signal 2 OFF detection timer
Set value
to
Setting/Checking: Contact output signal 1 function
45.
Press the [SEL] key once.
Setting screen of contact output signal 1 function is displayed on the digital display.
PV
SV
5.21 Communication function
5-80
Explanation
S etting/checking is possible only when the
contact input signal 2 is set to external switch
signal input (N.O. or N.C.).
Setting of the contact input signal 2 delay
timer for reading
Setting range: 0 to 300 seconds
Explanation
Setting/checking is possible only when the
contact input signal 2 is set to external switch
signal input (N.O. or N.C.).
Setting of the contact input signal 2 OFF
detection timer
Setting range: 0 to 10 seconds
Initial value
(Default setting)
Initial value
(Default setting)