SMC Networks HRS100-A?-20-? Operation Manual page 103

Thermo chiller
Hide thumbs Also See for HRS100-A?-20-?:
Table of Contents

Advertisement

2.
Press the [SEL] key 14 times.
Resetting screen of the pump accumulated operating time appears on the digital display.
PV
SV
3.
Select
and press [SEL] key to enter, and the accumulated operating time of the pump will be
reset. The display returns to the main menu.
Set value
Reset of accumulated operating time of the fan
4.
Press and hold the [MENU] key for approximately 2 seconds.
Repeat pressing the key until the key -lock setting screen [
display.
PV
SV
5.
Press the [SEL] key 15 times.
Resetting screen of the fan accumulated operating time appears on the digital display.
PV
SV
6.
Select
and press [SEL] key to enter, and the accumulated operating time of the fan
will be reset. The display returns to the main menu.
Set value
HRS Series
with [▲] key or [▼] key, and press [SEL] key to enter. Select
Table 5.16-2 Resetting of accumulated operating time of the fan
Explanation
No data reset.
Resets the accumulated operating time of the
pump.
Press and
hold [MENU]
key.
PV
SV
with [▲] key or [▼] key, and press "SEL" key to enter. Select
Table 5.16-3 Reset setting
Explanation
No data reset.
Resets the accumulated operating time of the
fan.
Chapter 5
Display and setting of various functions
Press and
hold [MENU]
key.
5.16Accumulated Operating Time Reset Function
HRX-OM-S004
Default
] appears on the digital
PV
SV
Default
5-37