Chapter 4
Starting the Product
7.
Press the [RESET] button (press the [▼] and [▲] buttons simultaneously) to reset the
alarm.
Pressing these buttons at the same time resets the alarm (low level in tank) and
turns OFF the [ALARM] LED (red) and the [
main menu screen, "Circulating fluid temp./Circulating fluid set temp.". Press the
[PUMP] button (press the [RUN/STOP] button and the [MENU] button
simultaneously) again to operate the pump individually.
Reset alarms on the "Alarm menu" screen.
Alarm reset is not accepted from any screen except the "Alarm menu" screen.
Refer to 5.2.1 Key operations.
OFF
OFF
8.
Repeat steps 1 to 4 to supply the circulating fluid to the user's equipment and piping.
Keep the fluid level in the tank between the "HIGH" and "LOW" levels of the fluid level
gauge of this product.
4.3 Preparation of circulating fluid
4-6
] LED. The display returns to the initial
Fig. 4-7 Alarm release
Press together
HRS Series