17.
Set the product operation when "Circulating fluid discharge pressure drop" alarm is
generated with [▲] key or [▼] key, and press [SEL] key to enter.
Table 5.20-15 Operation setting when "Circulating fluid discharge pressure drop" alarm is generated
Set value
Setting/Checking: Threshold pressure setting for "Circulating fluid discharge pressure drop" alarm
18.
Press the [SEL] key once.
Threshold detecting pressure setting screen for "Circulating fluid discharge pressure
drop" alarm generation appears on the digital display.
PV
SV
19.
Set the threshold detection pressure for "Circulating fluid discharge pressure drop"
alarm generation with [▲] key or [▼] key, and press [SEL] key to enter.
Table 5.20-16 Threshold detecting pressure setting for "Circulating fluid discharge pressure drop" alarm generation
Set value
MPa
to
PSI
to
HRS Series
Explanation
This alarm is not detected.
Operation continues when this alarm is
generated.
Operation stops when this alarm is generated.
Explanation
Setting/checking are not available if the
setting of the circulating fluid discharge
pressure rise is OFF.
Sets detection pressure for the circulating
fluid discharge pressure drop.
Pressure unit is MPa : Setting unit is
0.01MPa
Pressure unit is PSI : Setting unit is 1PSI
Chapter 5
Display and setting of various functions
HRX-OM-S004
Initial value
(Default setting)
Initial value
(Default setting)
5.20Alarm customizing function
5-57