Jogging Operation Function; Relation Between Torque Boost And V/F Characteristics - Omron 3G3JX User Manual

Sysdrive jx series compact simplified inverters
Hide thumbs Also See for 3G3JX:
Table of Contents

Advertisement

Jogging Operation Function

The motor rotates while the input is turned ON.
For details on the operation and settings, refer to "Jogging Operation" (page 4-48).
Parameter No.
Function name
A038
Jogging frequency
A039
Jogging stop selection
Related functions
•The Inverter runs at the speed set in A038 while the JG terminal allocated to one of the multi-
function input terminals is turned on. Stop selection is also available in A039.

Relation Between Torque Boost and V/f Characteristics

Determine the relation of output voltage against output frequency.
Parameter No.
Function name
A041
Torque boost selection
*
A241
2nd torque boost selection
A042
Manual torque boost voltage
*
A242
2nd manual torque boost voltage
A043
Manual torque boost frequency
2nd manual torque boost
*
A243
A044
V/f characteristics selection
*
A244
2nd V/f characteristics selection
A045
Output voltage gain
A245
2nd output voltage gain
Related functions
* To switch to the 2nd control, allocate 08 (SET) to the multi-function input terminal and then turn it on.
0.00/Starting frequency to 9.99
00: Free-run stop
01: Deceleration stop
02: DC injection braking stop
00: Manual torque boost
01: Automatic (simple) torque boost
0.0 to 20.0
(Ratio to the value of AVR voltage
selection A082)
0.0 to 50.0
(Ratio to base frequency)
frequency
00: Constant torque characteristics
(VC)
01: Reduced torque characteristics
(VP 1.7th power)
06: Special reduced torque
characteristics (Special VP)
20. to 100.
Data
Default setting
C001 to C005, JG input
Data
A082, H003/H203, H004/H204
4-2 Function Mode
Unit
6.00
Hz
00
Default setting
Unit
00
5.0
%
0.0
2.5
%
0.0
00
100.
%
4-12