Names of Parts
Main circuit
terminal block
(input side)
Digital Operator
For factory
maintenance only
Do not touch
Communications
connector
Emergency shut
off function
Relay output
selector (S8)
terminal block
OPE/485
communications
Main circuit
selector (S7)
terminal block
(output side)
Control circuit
terminal block
Installation and Wiring
Dimensions
W
W1
3G3JX-
W
W1
H
A2002-E, AB002-EF
80
67
155
A2004-E, AB004-EF
A2007-E
A4004-EF, AB007-EF
110
98
189
AB015-EF, AB022-EF
A2015-E, A2022-E, A2037-E, A4007-EF,
A4015-EF, A4022-EF, A4040-EF,
A2055-E, A2075-E,
180
164
250
A4055-EF, A4075-EF
Standard Connection Diagram
DC reactor
3-phase 200 VAC
Single-phase 200 VAC
3-phase 400 VAC
+1
+
R/L1
(L1)
S/L2
(/)
T/L3
(N)
L
PCS
Multi-function input
1
1
2
2
3
3
4
4
5
5
Common
P24
Power supply
H
Frequency
Frequency reference
Frequency
reference
O
reference
Common
1k ~ 2 kΩ
L
(voltage)
OI
Frequency reference
(current)
* Connect a single-phase 200 VAC input to terminals L1 and N.
* Factory default settings for relay output are NC contact for AL1 and NO contact for AL2.
Terminal symbols, Screw size and Tightening Torque
A2002 to A2007
Type
Terminal symbol
AB002 to AB004
AB007 to AB022
Main
R/L1,S/L2,T/L3
M3.5
circuit
U/T1, V/T2, W/T3
0.8 N·m
Ground
(max. 0.9 N·m)
(symbol)
Option
-,+,+1
Control
AM,H,O,OI,L
M2 / 0.2 N·m (max. 0.25 N·m)
circuit
5, 4, 3, 2,1,L,
PCS,P24, CM2,11
Relay
AL0,AL1,AL2
M2.5 / 0.5 N·m (max. 0.6 N·m)
Ground
M4
* For AB@ @ @ , L1, /, N are indicated instead R/L1, S/L2, T/L3 respectively.
Keys
Name
Mode key
Switches between the command setting and the data
settings, and between the basic function mode and the
expended function mode.
Status transition
* Hold down the Mode key for 3 seconds to jump to
'd001'.
Increment key
Changes the set values, parameters and
Commands.
Decrement key
RUN key
Starts the operation. Forward/Reverse rotation
depends on the 'F004' setting.
STOP/RESET
Stops the operation. Functions as the Reset key if an
key
error occurs.
H1
D
Enter key
Enters and stores the data.
143
95.5
109.5
132.5
176
130.5
157.5
235
167.5
[mm]
Parameter List
Regenerative Braking unit
Parameter
Function name
No.
d001
Output frequency moni-
-
tor
U/T1
M
V/T2
d002
Output current monitor
W/T3
d003
Rotation direction moni-
tor
d004
PID feedback value
monitor
AL1
Relay output
d007
Output frequency moni-
AL2
tor (after conversion)
Common
AL0
Multi-function
d013
Output voltage monitor
output
11
d016
Total RUN time
Common
CM2
d017
Power ON time monitor
d018
Fin temperature monitor 0.0 to 200.0
AM
Analog monitor
d080
Fault frequency monitor
output
d081
Fault monitor 1 (latest)
d082
Fault monitor 2
d083
Fault monitor 3
d102
DC voltage monitor
d104
Electric thermal monitor
F001
Output frequency set-
ting / monitor
A2015 to A2037
F002/F202
Acceleration time1/2nd
A2055 to A2075
A4004 to A4037
acceleration time1
A4055 to A4075
F003/F203
Deceleration time1/2nd
M4
M5
deceleration time1
1.2 N·m
3.0 N·m
F004
Operator rotation direc-
(max. 1.3 N·m)
(max. 3.3 N·m)
tion selection
A001/A201
Frequency reference
selection/2nd frequency
reference selection
A002/A202
RUN command selec-
tion/2nd RUN command
selection
M5
A003/A203
Base frequency/
2nd base frequency
A004/A204
Maximum frequency/
2nd maximum frequency
A005
O/OI selection
Description
A020/A220
Multi-step speed
reference0/2nd
multi-step speed
reference0
A021 to
Multi-step speed
A035
reference1~15
A038
Jogging frequency
A039
Jogging stop selection
A045/A245
Output voltage gain/ 2nd
output voltage gain
A097
Acceleration pattern
selection
A098
Deceleration pattern
selection
b001
Retry selection
b002
Allowable momentary
power interruption time
b083
Carrier frequency
b084
Initialization selection
b130
Overvoltage LAD stop
function
b131
Overvoltage LAD stop
function level
Parameter
No.
C001/C201
Multi-function input1
Monitor or data range
selection/2nd
multi-function input1
0.0 to 400.0
selection
C002/C202
Multi-function input2
0.0 to 999.9
selection/2nd
F:forward/o:stop/r:reverse
multi-function input2
selection
0.00 to 9999
C003/C203
Multi-function input3
(Valid when the PID function is selected.)
selection/2nd
0.00 to 9999
multi-function input3
1000 to 3996 (at 10000 to 39960)
selection
(Output frequency × conversion factor of b086)
C004/C204
Multi-function input4
0 to 600
selection/2nd
multi-function input4
0 to 9999
selection
0 to 9999
C005/C205
Multi-function input5
selection/2nd
multi-function input5
0 to 9999
selection
Error code (condition of occurrence) →
Output frequency → Output current →
C011 to
Multi-function input 1-5
Internal DC voltage → RUN time → ON time
C015
operation selection
C021
Multi-function output
0.0 to 999.9
terminal 11 selection
0.0 to 100.0
C026
Relay output (AL1,AL2)
Starting frequency to max. frequency
function selection
0.01 to 3000
0.01 to 3000
C028
AM selection
00:forward/01:reverse
C031
Multi-function output
Terminal 11 contact
00:Digital Operator (volume)/01:Terminal/
selection
02:Digital Operator (F001)/
C036
Relay output (AL1,AL2)
03:Modbus communication/
contact selection
10:Frequency operation result
H003/H203
Motor capacity
01:Terminal/02:Digital Operator/
selection/2nd motor
03:Modbus communication
capacity selection
H004/H204
Motor pole number
30 to max. frequency [A004/A204]
selection/2nd motor pole
number selection
30 to 400
02: Switch between O/Volume via terminal AT
03: Switch between OI/Volume via terminal AT
04: O input only/05:OI input only
0.0/Starting frequency to max. frequency
OMRON shall not be responsible for conformity with any standards, code,
or regulations that apply to the combination of products in the customer's
application or use of the products.
0.0/Starting frequency to max. frequency
Take all necessary steps to determine the suitability of the product for the systems, machines, and
equipment with which it will be used.
0.00/Strating frequency to 9.99
Please know and observe all prohibitions of use apllicable to the products.
00:Free run on jogging stop
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
01:Deceleration stop on jogging stop
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
02:DC injection braking on jogging stop
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND IN-
STALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
20 to 100
See also product catalogs for Warranty and Limitations of Liability.
00:Line/01:S-shape curve
Sales and Service: OMRON EUROPE B.V
00: Alarm/01:0 Hz start
02: Frequency matching start
03: Trip after frequency matching deceleration
OMRON Corporation
stop
Industrial Automation Company
0.3 to 25.0
Control Devices Division H.Q.
Motion Control Division
2.0 to 12.0
Shiokoji Horikawa, Shimogyo-ku,
00:Clear the trip monitor
Kyoto, 600-8530 Japan
01:Initialize data
Tel: (81) 75-344-7173
02:Clear and initialize
Fax: (81) 75-344-7149
00:Disable/01:Enable
2-2-1 Nishikusatsu, Kusatsu-shi,
Shiga, 525-0035 Japan
200V class:330 to 395
Tel: (81) 77-565-5223
400V class:660 to 790
Fax: (81) 77-565-5568
Manufacturer: Hitachi Industrial Equipment Systems Co.,Ltd.
Note:
In the interest of product improvement, specifications are subject to change without notice
Printed in Japan
Function name
Monitor or data range
00:FW(forward)/01:RV(reverse)/
02:CF1(multi-step speed setting binary1)/
03:CF2(multi-step speed setting binary2)/
04:CF3(multi-step speed setting binary3)/
05:CF4(multi-step speed setting binary4)/
06:JG(jogging)/07:DB(external DC injection/
braking)/08:SET(2nd control)/09:2CH(2-step
acceleration/deceleration)/11:FRS(free run
stop)/12:EXT(external trip)/13:USP(USP func-
tion)/15:SFT(soft lock)/16:AT(analog input
switch)/18:RS(reset)/19:PTC(thermistor input)/
20:STA(3-wire start)/21:STP(3-wire stop)/22:F/
R(3-wire forward/reverse)/23:PID(PID enable/
disable)/24:PIDC(PID integral/reset)/
27:UP(UP/DWN function accelerated)/
28:DWN(UP/DWN function decelerated)/
29:UDC(UP/DWN function data clear)/
31:OPE(forward operator)/50:ADD(frequency
addition)/51:F-TM(forced terminal block)/
52:RDY(ready function)/53:SP-SET(special
2nd function)/64:EMR(emergency shut off)/
255:No function
00:NO
01:NC
00:RUN(during RUN)/01:FA1(constant speed
reached)/02:FA2(set frequency min. reached)/
03:OL(overload warning)/04:OD(PID exces-
sive deviation)/05:AL(alarm output)/06:Dc(dis-
connection defected)/07:FBV(PID FB value
output)/08:NDc(Network error)/09:LOG(logic
operation output)/10:ODc(communication
option, disconnected)/43:LOC(light load defec-
tion)
00:Output frequency/01:Output current
00:NO contact at AL1, NC contact at AL2
01:NC contact at AL1, NO contact at AL2
200V class: 0.2 to 7.5
400V class: 0.4 to 7.5
2/4/6/8
SUITABILITY FOR USE
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel. (31)2356-81-300
Fax: (31)2356-81-388
.

Advertisement

loading

Summary of Contents for Omron 3G3JX-A2002-E

  • Page 1: Instruction Manual

    PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO 02:DC injection braking on jogging stop ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND IN- STALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
  • Page 2 30-16 0.16-0.19 0.22-0.25 connectors • Comply with the local ordinance and regulations when disposing of the product. Relay connector 30-14 0.37-0.44 0.5-0.6 OMRON Corporation Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530, Japan Omron Europe B.V. Wegalaan 67-69, NL-2132 JD Hoofddorp, The Netherlands...

This manual is also suitable for:

3g3jx- ab002-ef3g3jx-a2007-e3g3jx-ab004-ef3g3jx-a2004-e3g3jx-a4004-ef3g3jx-ab007-ef ... Show all