Fault Monitors; Dc Voltage Monitor; Electronic Thermal Monitor - Omron 3G3JX User Manual

Sysdrive jx series compact simplified inverters
Hide thumbs Also See for 3G3JX:
Table of Contents

Advertisement

Fault Monitors 1[d081], 2[d082], 3[d083]
Displays the details of the last three trips.
The most recent trip is displayed on trip monitor 1.
(Display)
•Factor (E01 to E60)
•Output frequency at the time of tripping (Hz)
•Output current at the time of tripping (A)
•Internal DC voltage at the time of tripping (V)
•Total RUN time before the trip (hr)
•Total power supply time before the trip (hr)
*1. Refer to "Error Code List" (page 5-1) and "Trip Monitor Display" (page 5-4).
(Trip Monitor Display Sequence)
(1)Trip factor
dk0k8k1
ekLk0k7
*2. Displays
DC Voltage Monitor [d102]
Displays the main circuit DC voltage of the Inverter.
(Display)
0.0 to 999.9
Electronic Thermal Monitor [d104]
Displays the count integration value of the electronic thermal. An overload trip occurs if it reaches
100% (E05).
(Display)
0.0 to 100.0
*1
*2
(2)Trip frequency
(3)Trip current
6k0.0
_k_k_k_
if there has been no trip.
: Displays in increments of 0.1 V.
: Displays in increments of 0.1%.
(4)Trip P-N voltage (5)Total RUN time (6)Power ON time
4.0
3k9k8.
4-1 Monitor Mode
1k5.
1k8.
4-4
4