4-2 Function Mode

Frequency Limit

This function limits the Inverter output frequency.
Parameter No.
A061
*
A261
A062
4
*
A262
Related functions
* To switch to the 2nd control, allocate 08 (SET) to the multi-function input terminal and then turn it on.
•You can set both upper/lower limits to the set frequency. This function does not accept any
frequency reference beyond the set limits.
•Set the upper limit first.
Make sure the upper limit (A061/A261) is higher than the lower limit (A062/A262).
•Neither limit would work if set to 0 Hz.
If the lower limit is set, the set value is prioritized even if 0 V (4 mA) is input for frequency reference.

Frequency Jump Function

This function helps avoid resonant points of loaded machines.
Parameter No.
A063
A065
A067
A064
A066
A068
Related functions
•The output frequency cannot be set within the frequency range set in the frequency jump function.
•The output frequency fluctuates continuously according to the acceleration/deceleration time
during both actions. The jump frequency can be set at up to three points.
4-19
Function name
0.0/Frequency lower limit [A062] to
Frequency upper limit
Max. frequency [A004]
2nd frequency upper
0.0/Frequency lower limit [A262] to
limit
Max. frequency [A204]
0.0/Starting frequency to Frequency
Frequency lower limit
upper limit [A061]
2nd frequency lower
0.0/Starting frequency to Frequency
limit
upper limit [A261]
Set frequency (Hz)
Max. frequency
A004/A204
A061
A062
0V
4mA
Function name
Jump frequency 1
Jump frequency 2
0.0 to 400.0
Jump frequency 3
Jump frequency width 1
Jump frequency width 2
0.0 to 10.0
Jump frequency width 3
Data
Default setting
C001 to C005
Frequency
reference
10V
20mA
Data
Default setting
C001 to C005
Unit
0.0
0.0
Hz
0.0
0.0
Unit
0.0
Hz
0.5