Advanced Operation
Set Values
This parameter is used to set the electronic thermal protection constant of motor over-
load detection OL1.
The default setting does not need any changes in normal operation.
To set the parameter according to the characteristics of the motor, confirm the thermal
time constant with the motor manufacturer and set the parameter with some margin. In
other words, set the value a little shorter than the thermal time constant.
To detect motor overloading more quickly, reduce the set value, provided that it does
not cause any application problems.

6-7-2 Cooling Fan Operation Function (n35)

This parameter is used to operate the cooling fan of the Inverter while the Inverter is
turned on or only while the Inverter is in operation.
Cooling Fan Operation Selection
n35
Setting
0, 1
range
Set Values
Value
0
The fan rotates only while the RUN command is input and for 1 minute after
the Inverter stops operating.
1
The fan rotates while the Inverter is turned on.
This parameter is available only if the Inverter incorporates a cooling fan.
If the operation frequency of the Inverter is low, the life of the fan can be prolonged by
setting the parameter to 0.
Unit of
1
setting
Description
Chapter 6
Changes during
No
operation
Default setting
0
6-15