Specifications of the Relay Output Terminals

•The relay output terminals are set to the SPDT contact. The following shows their operations.
Electrical specifications
Output terminal
MA-MC
MB-MC
(a) When used as an alarm terminal
C036
Power
Inverter
set
supply
status
value
Fault
ON
00
Normal
OFF
Fault
ON
01
Normal
OFF
Resistance load
Max. contact
250 V AC, 2 A
capacity
30 V DC, 3 A
Min. contact
100 V AC, 10 mA
capacity
5 V DC, 100 mA
Max. contact
250 V AC, 1 A
capacity
30 V DC, 1 A
Min. contact
100 V AC, 10 mA
capacity
5 V DC, 100 mA
MB
Inside the Inverter
(Factory default)
Output terminal status
MA-MC
MB-MC
Closed
Open
Open
Closed
Open
Closed
Open
Closed
Closed
Open
Open
Closed
Inductive load
250 V AC, 0.2 A
30 V DC, 0.6 A
250 V AC, 0.2 A
30 V DC, 0.2 A
MA MC
(b) When used as an output terminal
C036
Power
Output
set
supply
signal
value
ON
ON
00
OFF
OFF
ON
ON
01
OFF
OFF
4-2 Function Mode
Output terminal status
MA-MC
MB-MC
Closed
Open
Open
Closed
Open
Closed
Open
Closed
Closed
Open
Open
Closed
4-72