4-2 Function Mode
Query
No.
Field name
1
Slave address*1
2
Function code
Register start address
3
*3
Register start address
4
*3
Number of holding
5
4
registers (MSB)
Number of holding
6
registers (LSB)
7
CRC-16 (MSB)
8
CRC-16 (LSB)
*1. Broadcasting cannot be performed.
*2. Data is transferred by the number of data bytes. In this example, 12 ("0Ch") bytes are used since 6 pieces of
holding register data are returned.
*3. Note that the holding register start address is "0011h", which is smaller by 1 than the register number "0012h".
Read the data received in the response, as follows:
Holding register start
Holding register start
4-85
Example
(Hex)
01
03
00
(MSB)
11
(LSB)
00
06
95
CD
Response buffer
12+0
number
(MSB)
Response data
Trip data
Trip factor (E03)
Response buffer
12+3
number
(MSB)
Response data
00h
Trip data
Response
No.
1
2
3
Number of data bytes
4
Register data 1 (MSB)
5
Register data 1 (LSB)
6
Register data 2 (MSB)
7
Register data 2 (LSB)
8
Register data 3 (MSB)
9
Register data 3 (LSB)
10
Register data 4 (MSB)
11
Register data 4 (LSB)
12
Register data 5 (MSB)
13
Register data 5 (LSB)
14
Register data 6 (MSB)
15
Register data 6 (LSB)
16
17
4-5
12+0
12+1
(LSB)
(MSB)
003h
00h
Not used
10-11
12-13
12+3
12+4
(LSB)
(MSB)
00h
001Eh
Not used
Output current (3.0 A)
Example
Field name
(Hex)
Slave address
Function code
*2
0C
1E
1C
CRC-16 (MSB)
AF
CRC-16 (LSB)
6D
6-7
8-9
12+1
12+2
(LSB)
(MSB)
00h
0063h
Frequency (9.9 Hz)
14-15
12+4
12+5
(LSB)
(MSB)
001Ch
DC bus V DC (284V)
01
03
00
03
00
00
00
63
00
00
00
01
12+2
(LSB)
12+5
(LSB)