4-2 Function Mode
The data received as the response shows the statuses of coils 7 to 14. The data received here, "05h
= 00000101b", should be read with setting coil 7 as LSB as follows:
Item
Data
Coil No.
14
13
12
11
10
9
8
7
Coil status
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
If the reading coil exceeds the defined coil range in the final coil data, such coil data is regarded as
"0" and returned.
Refer to "<Exception Response>" (4-89) if the coil status reading command has not been performed
normally.
<Reading the Holding Register Content [03h]>
4
Reads the specified number of consecutive holding register contents from the specified holding
register addresses.
(Example)
•Reads the latest trip information (frequency, current, voltage at trip) from the Inverter with the slave
address "1".
•Refer to the trip status as follows:
D081
D081
3G3JX command
D081 (Factor)
D081 (Frequency)
(Output current)
(DC bus V DC)
Register No.
0012h
0014h
0016h
0017h
Trip status
Overcurrent (E03)
9.9 Hz
3.0 A
284 V
4-84