The Power + Built - In Web Interface; F Igure 119: P Ower + Controller Rear Panel - Gamatronic Power+ User Manual

Power+ rm 50 kva, n.am. std modular ups system
Hide thumbs Also See for Power+:
Table of Contents

Advertisement

11. T
P
HE
OWER
The Power+ Web interface enables you to control your Power+ unit from a distance over an
Ethernet network, using an HTML browser interface.
11.1.1
Preliminaries to use of the Web interface
To enable the Power+ Web interface:
1.
Consult with your Network Administrator to obtain an IP address for your Power+, and the
appropriate mask and gateway address.
2.
Configure the Power+ with the IP address. This is done from the Power+ main menu as
follows:
a.
Setup > (enter your password, then press Ent; default password is 8 left arrows) >
Service > SC2012 > Network.
b.
From the Network menu, choose IP Address and enter the assigned IP address.
c.
From the Network menu, choose Gateway and enter the assigned Gateway
address.
d.
From the Network menu, choose Mask and set the assigned subnet mask.
e.
From the Network menu choose Store to save the information just entered.
3.
Connect the Power+ to the local Ethernet network using the Ethernet (RJ45) port on the
rear panel of the Power+ controller. This is the port labeled "TCP/IP Port" on the left side
of the controller rear panel in Figure 119 below.
4.
On a computer terminal that has connectivity to the Power+ IP address, open a Web
browser and enter the Power+ IP address in the URL bar. For example: "//192.102.2.130"
(without quotation marks), and press Enter. You should see the Web interface main
screen (see Figure 120 below).
74
+
-
W
BUILT
IN
Figure 119: Power+ controller rear panel
POWER + RM 50
Gamatronic Electronic Industries Ltd.
EB INTERFACE
VA, N.Am. Std. – User Guide, Release 1.4
K

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents