POWER + shutdown (switching to bypass)

5.2
Switch the load OFF.
1.
Press twice on the On/Off button.
2.
Wait 2 minutes for the POWER + to shut down. The control screen will indicate UPS
3.
OK (OFF).
Note: This does NOT switch the entire POWER + OFF. Power is still delivered to the load but in
bypass.

POWER + total shutdown (no ac output)

5.3
Switch the load OFF.
1.
Press and hold the On/Off button for 10 seconds.
2.
The control screen will indicate UPS OK (OFF).
3.
POWER + RM 50
VA, N.Am. Std. – User Guide, Release 1.4
K
35