Gamatronic Power+ User Manual page 110

Power+ rm 50 kva, n.am. std modular ups system
Hide thumbs Also See for Power+:
Table of Contents

Advertisement

UPS capacity
Dimensions (U.S. measurements) incl. exterior cabinet, excl. batteries
Height
Width
Depth
Weight (lbs)
Dimensions (metric measurements) incl. exterior cabinet, excl. batteries
Height
Width
Depth
Weight (kg)
Acoustic Noise
Noise (dBA) with half load
Noise (dBA) with full load
SYSTEM CONTROLLER – TECHNICAL DATA
Micro Controller core
Display
Other indicators
Analog input channels
Digital input channels
Real Time Clock (RTC)
Power meter
Volt-free outputs (dry contacts)
RS232 user port
Optional communication
Communications with system modules
Events log
System operation without controller
On-screen parameters
Alarms
RTC operation without power
Power requirements
100
10 kVA
20 kVA
42U / 80 in (including cabinet legs)
766
788
42U / 2020 mm (including cabinet legs)
347.4
357.6
48
52
51
54
16 bit
4 × 40 characters LCD with backlight
8 LEDs, buzzer
4
8
Yes, with backup
kVA, kW, PF
6 outputs, rated 50V/1A
Yes, isolated
TCP/IP, GPRS/SMS Wireless
communications(Optional)
Serial, isolated
255 events
Unchanged
Load bar-graph
3-phase voltages
3-phase currents
Battery voltage
Status of each UPS module
Static-switch parameters and status
Battery sensor temperature
AC failure
DC failure
UPS module(s) failure
Load on bypass
Battery test failure
Over/under temperature
Overload
(Contacts rated max. 48 V 1 A)
2 weeks
3 × 208 Vac / ±216 Vdc, 15W
POWER + RM 50
Gamatronic Electronic Industries Ltd.
30 kVA
40 kVA
24 in
39.4 in
811
833
600 mm
1000 mm
367.8
378.0
53
54
55
57
VA, N.Am. Std. – User Guide, Release 1.4
K
50 kVA
856
388.2
55
58

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents