The Main Menu And Its Options; Table 7: Main Menu Options - Gamatronic Power+ User Manual

Power+ rm 50 kva, n.am. std modular ups system
Hide thumbs Also See for Power+:
Table of Contents

Advertisement

11.3

The Main Menu and its options

The Main Menu of Power+'s built-in remote management software consists of a column of option
buttons on the left side of the Main Screen (see Figure 120 on page 75).
Table 7 below lists the options in the Main Menu column on the Main Screen, and describes each
option briefly. Each option is described in greater detail in the subsequent sections.
M
D
ENU OPTION
Main
Displays a condensed system status: Alarm status and basic readings.
Shows real-time readings for each input and output phase: voltage, current,
Analysis
kVA, kW, power factor.
Load
Shows current load level (0 ~ 110 %) for each input and output phase.
Displays status of an individual UPS module, shows input and output ac
Modules
voltages and current, dc voltage, active alarms if any.
Displays status of Static Switch, including inverter output voltages and
STSW
frequency, bypass voltages and frequency, active alarms if any.
Power+ Log
Displays system log, data can be printed or exported to an Excel file.
From this screen, the following system commands can be executed: Move
load to bypass, move load to inverter, start battery test, abort battery test,
LEDs test, shutdown, startup, restart, simulate load on battery condition,
simulate battery status is low.
Power+ Control
Use of this option is disabled by factory default. To enable (or disable), from
the Power+ console main menu choose the following:
(7) Setup > (8) Service > (5) Config > (8) Rem Command
Send SMS messages from this screen (WING module must be present).
Send SMS
SMS Log
View SMS message log (WING module must be present).
Displays reading from optional temperature sensor (connected to the two
Temperature
temperature sensor terminals on the rear of the controller module.
Configure the settings of the remote management software.
Configuration
The Main Manu options are described in more detail below.
76

Table 7: Main Menu options