4.2

Over-Voltage Protection

Ensure that the lines into and out of the UPS have protective circuit breakers installed in
accordance with the ratings listed in Table 1 for your Power+ model.
22
CAUTION!
To reduce the risk of fire, connect the UPS only to a circuit
provided with maximum branch circuit over-current protection
as indicated in Table 1, in accordance with the National Electric
Code, NSI/NFPA 70.
ATTENTION !
Pour réduire le risque du feu, reliez L'UPS seulement à un circuit équipé de
protection maximum de surintensité de circuit de branche comme indiqué
au tableau 1, selon le code électrique national, au NSI/NFPA 70.
Table 1: Required over-current protection
POWER+
output
capacity
Ac input
10 kVA
Load
Battery dc input
Ac input
20 kVA
Load
Battery dc input
Ac input
30 kVA
Load
Battery dc input
Ac input
40 kVA
Load
Battery dc input
Ac input
50 kVA
Load
Battery dc input
POWER + RM 50
Gamatronic Electronic Industries Ltd.
Maximum
Line
over-current
protection
35 A
30 A
70 A
60 A
110 A
90 A
150 A
125 A
175 A
150 A
VA, N.Am. Std. – User Guide, Release 1.4