The "Power+ Control" main menu option enables the user to initiate any of a number of UPS
processes. The commands available are described in Table 10 below.
Table 10: Commands available on the "Power+ Control" screen
M
ENU OPTION
Load on bypass
Load on inverter
Start battery test
Abort battery test
LED test
Shutdown
Startup
Restart
At the bottom of the "Power+ Control" screen are two links:
82
Figure 125: The "Control" main menu option screen
D
ESCRIPTION
Transfers the load to the bypass voltage.
Transfers the load to the inverter.
Initiates a battery test. Note: it is recommended that a battery test not be
initiated when the when the UPS is operating near 100 % capacity
and at the same time the battery is known to be not fully charged
or not connected or otherwise faulty.
Stop a battery test immediately.
The UPS beeps briefly and all of the LEDs on the control panel light up, to
reveal any faulty LEDs.
Shuts down the Power+. Power will continue to be available to the loads
from the bypass voltage.
Starts up the Power+ when it is in an "OFF" condition.
When the Power+ is "ON", this command initiates a shutdown of the
Power+ followed by a startup.
POWER + RM 50
Gamatronic Electronic Industries Ltd.
VA, N.Am. Std. – User Guide, Release 1.4