Gamatronic Electronic Industries Ltd.
7.1.3
Self-test
From the main menu select option 3 (SELF TEST) to run a self-test of the
POWER + . The self-test displays the window shown in Figure 46. You can run
a self-test at any time without interfering in the normal operation of the
POWER + . A self-test is also initiated by the POWER + itself each day at
midnight.
The failure of a self-test sets on the self-test alarm. The self-test alarm can only
be cleared by a subsequent successful self test, or it can be cleared manually
by a maintenance technician. Powering the POWER + down and up, for
example, does not clear the self-test alarm. This is because the failure of a self-
test is considered a serious event that should not be "forgotten". A self-test
failure is also recorded in the alarm log.
Main
menu
Option 3
7.1.4
History (logs)
From the main menu select option 4 (HISTORY) to display the window shown in Figure 47. The
last 255 events reserved in the LOG are displayed, as shown in Figure 48.
Navigate the LOG by scrolling using the ▲ and ▼ keys.
Main
menu
Option 4
Navigate the LOG by scrolling using the ◄ and ► keys.
Main
menu
Option 4
Table 3 below itemizes the log messages that appear on the controller panel.
POWER + RM 50

Figure 46: Result screen from self-test

Figure 47: History logs

Figure 48: History log scroll

VA, N.Am. Std. – User Guide, Release 1.4