FreedomHF_IC_01-Installation.fm Page 23 Monday, December 24, 2007 9:47 AM
CAUTION: Equipment damage
Do NOT connect the AC OUT Neutral and Line
to the AC IN Neutral and Line.

Figure 1-7 AC Wiring Diagram without an Inverter Subpanel

975-0395-01-01
See Important note below.
Input breakers must
be provided by
installers.
In this wiring diagram, the AC input to the
from an AC source. The AC source input wiring must be protected by an
AC breaker of 30 A max. The output wiring is routed to the main AC
panel which is also protected by AC breakers or circuit breakers.
Important:
The generator must have its neutral bonded to ground. If it is not
bonded, a bonding jumper must be installed between the neutral and ground at
the generator's output or at the generator side of the transfer switch.
Also, the main AC panel must not have a permanent neutral to ground bond
installed.