Table 1-2 Recommended Cable Sizes

Inverter/Charger
Freedom HF 1000
Freedom HF 1800
Note: Xantrex recommends not using a cable longer than 5 feet (1.5 meters) in each direction. Cable
sizes above are based on the US National Electrical Code Table 310.17 - 75C cables, assuming an
ambient temperature of 30
Important:
performance of the
HF
too small the voltage drop from this surge will result in a voltage at the
HF
Freedom HF
load such as a microwave or refrigerator attempts to start - then the unit may
work correctly sometimes and not work correctly other times.
DC Disconnects
The DC circuit from the battery to the Freedom HF must be equipped
and Over-
with a disconnect and over-current device. This usually consists of a
Current Devices
circuit breaker, a "fused-disconnect," or a separate fuse and DC
disconnect. Do not confuse AC circuit breakers with DC circuit breakers.
They are not interchangeable. The rating of the fuse or breaker must be
matched to the size of cables used in accordance with the applicable
installation codes. The breaker or disconnect and fuse should be located
as close as possible to the battery, in the positive cable. Applicable codes
may limit how far the protection can be from the battery.
Batteries
The
requires a deep-cycle battery or group of batteries that provide the DC
current that the
1–10
Cable Length: Battery
to Inverter (one way)
Minimum Cable Size
Less than 5 feet (1.5
No. 2 AWG
meters)
Less than 5 feet (1.5
No. 2/0 AWG
meters)
°
C cables.
Using the correct cable size is critical to achieving the rated
Freedom HF
can draw current surges from the battery of up to 400A. If the DC wiring is
terminals that is too low for the
may appear to operate correctly with smaller cables until a heavy
Freedom HF
uses 12-volt battery banks. Every
Freedom HF
This guide for use by qualified installers only
Maximum battery Fuse
Size
150 Adc
250 Adc
unit. When starting a heavy load the
Freedom HF
to operate correctly. The
Freedom HF
converts to AC.