X-Slot Connections; Figure 4-19. X-Slot Communication Bays - Eaton Power Xpert Plus 1 Installation And Operation Manual

450–550 kva
Table of Contents

Advertisement

4.7.3

X-Slot Connections

NOTE LAN and telephone drops for use with X-Slot cards must be provided by the customer.
NOTE When installing external wiring to X-Slot cards, conduit must be installed to the UPS cabinet. When
installing internal wiring to X-Slot terminals, route the wiring through the internal opening in the X-Slot
communication bay.
For installation and setup of an X-Slot card, contact an Eaton service representative
(see page 1-10).
To install wiring to connections:
1.
2.
3.
4.
5.
6.
7.
X-Slot Communication Bay 1
X-Slot Communication Bay 3
t
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
If not already installed, install the LAN and telephone drops.
Unfasten the front door latch and swing the door open (see Figure 4‐2 on
page 4-4).
Remove the UPS cabinet interface entry conduit landing plates to drill or punch
holes (see Figure 4‐4 on page 4-8).
Reinstall the interface entry plates and install the conduit.
Route and install the LAN, telephone, and other cables to the appropriate X-Slot
cards. See Figure 4‐13 on page 4-19 and Figure 4‐19 for X-Slot communication
bay locations.
Close the front door and secure the latch.
Refer to the manual supplied with the X-Slot card for operator instructions.
Figure 4‐19. X-Slot Communication Bays
X-Slot Communication Bay 2
X-Slot Communication Bay 4
S
164201701 Rev 3 www.eaton.com/powerquality
UPS SYSTEM INSTALLATION
4-25

Advertisement

Table of Contents