Transfer From Online To Bypass Mode - Eaton Power Xpert Plus 1 Installation And Operation Manual

450–550 kva
Table of Contents

Advertisement

UPS OPERATING INSTRUCTIONS
t
7-14
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
On the System Status screen, the UPS status should indicate SHUTDOWN and the
9.
UPM status should indicate OFFLINE.
10. Verify no alarms are active.
11. On the System Status screen, select the
Command screen screen is displayed.
12. On the UPS Control Command screen, select the UPM to start.
13. Press the
CONTROLS
UPM Control Command screen is displayed.
14. On the UPM Control Command screen, select
15. Press the
SELECT
16. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM rectifier and inverter turn on.
17. To transfer the UPM to Online mode, press the
UPS Control Command menu bar. The UPM Control Command screen is
displayed.
18. On the UPM Control Command screen, select
19. Press the
SELECT
The UPM transfers to Online mode. The UPM status indicates ONLINE.
7.3.5

Transfer from Online to Bypass Mode

To transfer the critical load to Bypass mode:
In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.
1.
Press the
CONTROLS
screen is displayed.
2.
On the System Status screen, select the
3.
Press the
CONTROLS
Control Command screen is displayed.
4.
On the Bypass Control Command screen, select
UPM
pushbutton on the UPS Control Command menu bar. The
pushbutton on the UPM Command menu bar.
pushbutton on the UPM Command menu bar.
C A U T I O N
pushbutton on the main menu bar. The System Status
BYPASS
pushbutton on the System Status menu bar. The Bypass
S
164201701 Rev 3 www.eaton.com/powerquality
command. The UPS Control
.
UPM ON
pushbutton on the
CONTROLS
.
UPM GO TO ONLINE
command.
.
GO TO BYPASS