Transfer From High Alert To Bypass Mode; Transfer From Energy Saver To High Alert Mode - Eaton Power Xpert Plus 1 Installation And Operation Manual

450–550 kva
Table of Contents

Advertisement

7.3.14

Transfer from High Alert to Bypass Mode

To transfer the critical load to Bypass mode:
NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer
Service Engineer.
1.
2.
3.
4.
5.
7.3.15

Transfer from Energy Saver to High Alert Mode

To transfer the critical load to High Alert mode:
NOTE The Energy Saver and High Alert mode commands are displayed only if enabled at the factory or by
an Eaton Customer Service Engineer.
1.
2.
3.
4.
5.
t
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
Press the
pushbutton on the main menu bar. The System Status
CONTROLS
screen is displayed.
On the System Status screen, select the
Press the
pushbutton on the System Status menu bar. The Bypass
CONTROLS
Control Command screen is displayed.
On the Bypass Control Command screen, select
Press the
pushbutton on the Bypass Command menu bar.
SELECT
The UPS transfers to Bypass mode and the critical load is immediately supplied
by the bypass source. If the bypass source is not available, the power module
remains on and an alarm sounds
status indicator is illuminated. The UPS status indicates BYPASS. The
The
BYPASS
Bypass status indicates ON. The UPM status indicates READY. The power
module remains on.
Press the
pushbutton on the main menu bar. The System Status
CONTROLS
screen is displayed.
On the System Status screen, select the
Press the
pushbutton on the System Status menu bar. The UPS
CONTROLS
Control Command screen is displayed.
On the UPS Control Command screen, select
Press the
pushbutton on the UPS Command menu bar.
SELECT
The UPS transfers to Battery mode and then to High Alert mode. After one hour
the UPS transfers to Energy Saver mode and the critical load is immediately
supplied by the bypass source. If the bypass source is not available, the power
module remains on and an alarm sounds.
status indicator is illuminated. The UPS status indicates HIGH
The
ONLINE
ALERT. The UPM status indicates ONLINE. The power module is on.
UPS OPERATING INSTRUCTIONS
command.
BYPASS
GO TO BYPASS
command.
UPS
GO TO HIGH ALERT
S
164201701 Rev 3 www.eaton.com/powerquality
.
.
7-19