Installing Mini-Slot Interface Connections - Eaton 93E UPS Installation And Operation Manual

15–80 kva (380/400/415v)
Table of Contents

Advertisement

UPS System Installation
6.
Route and install pull chain wiring (Twisted Wires 0.5-2.0 mm
MOBs. See Figure 4-7 , Figure 4-10 and Figure 4-11 for wiring information.
7 .
If wiring Mini-Slot connections, proceed to paragraph 4.5.3;

4.5.3 Installing Mini-Slot Interface Connections

For installation and setup of an Mini-Slot card, contact an Eaton service representative (see paragraph 1.8)
To install wiring:
1.
If not already installed, install the LAN drop.
2.
Route and install the LAN and other cables to the appropriate Mini-Slot cards. See Figure 4-6 and Figure 4-7
for Mini-Slot communication bay locations.
3.
Refer to the manual supplied with the Mini-Slot card for operator instructions.
4.
Install the power terminal cover using the provided hardware.
4-12
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
NOTE
LAN drop for connection to UPS communications card is to be supplied by customer.