Building Alarm Monitoring; General Purpose Relay Contact; Remote Monitor Panel Ii; Figure 8‐3. Remote Monitor Panel Ii - Eaton Power Xpert Plus 1 Installation And Operation Manual

450–550 kva
Table of Contents

Advertisement

8.6

Building Alarm Monitoring

8.7

General Purpose Relay Contact

8.8

Remote Monitor Panel II

t
Power Xpert
This standard feature lets you connect the UPS to your building alarms, such as
smoke detectors or overtemperature alarms. The customer interface terminals for
external connections are located inside the UPS. You should use twisted-pair wires
for each alarm input and common.
The building alarms can be programmed to display the alarm functional name.
One general purpose relay contact is provided as a standard feature on the UPS. The
alarm contact is located inside the UPS on the customer interface terminal board.
You can use a normally-closed or normally-open contact. If the state of the contact
changes from the state you specify as normal, a signal is issued. You can connect this
contact to equipment at your facility (such as a light or an alarm bell) to let you know
when an alarm is active on the UPS. This feature is useful if the UPS is located in a
remote area where the UPS horn may not be heard immediately.
Contacts should not be operated in excess of 30 Vac @ 5A maximum.
As an option, an RMP II can be installed to monitor the operation of the UPS system
from virtually any location within the facility, up to 150m (500 ft) from the UPS. The
RMP II contains backlit status indicators and a local horn. The RMP II can be
flush‐mounted or surface‐mounted on a desktop, or secured to a wall. Figure 8‐3
shows an RMP II.
9395 UPS (450–550 kVA) Installation and Operation Manual
C A U T I O N
Figure 8‐3. Remote Monitor Panel II
S
164201701 Rev 3 www.eaton.com/powerquality
COMMUNICATION
8-7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power xpert 9395

Table of Contents