Transfer From Energy Saver To High Alert Mode; Transfer From High Alert To Bypass Mode - Eaton Power Xpert Plus 1 Installation And Operation Manual

450–550 kva
Table of Contents

Advertisement

7.4.14

Transfer from High Alert to Bypass Mode

To transfer the critical load to Bypass mode:
NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer
Service Engineer.
1.
2.
3.
4.
5.
7.4.15

Transfer from Energy Saver to High Alert Mode

To transfer the critical load to High Alert mode:
NOTE The Energy Saver and High Alert mode commands are displayed only if enabled at the factory or by
an Eaton Customer Service Engineer.
1.
2.
3.
4.
5.
t
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
On any UPS, press the
CONTROLS
Status screen is displayed.
On the System Status screen, select the
Press the
pushbutton on the System Status menu bar. The Bypass
CONTROLS
Control Command screen is displayed.
On the Bypass Control Command screen, select
Press the
pushbutton on the Bypass Command menu bar.
SELECT
All of the UPSs transfer to Bypass mode and the critical load is immediately
supplied by the bypass source. If the bypass source is not available, the power
module remains on and an alarm sounds.
status indicator is illuminated. The UPS status indicates BYPASS. The
The
BYPASS
Bypass status indicates ON. The UPM status indicates READY. The power
module remains on.
On any UPS, press the
CONTROLS
Status screen is displayed.
On the System Status screen, select the
Press the
pushbutton on the System Status menu bar. The UPS
CONTROLS
Control Command screen is displayed.
On the UPS Control Command screen, select
Press the
pushbutton on the UPS Command menu bar.
SELECT
All of the UPSs transfer to Battery mode and then to High Alert mode. After one
hour the UPSs transfer to Energy Saver mode and the critical load is immediately
supplied by the bypass source. If the bypass source is not available, the power
module remains on and an alarm sounds.
status indicator is illuminated. The UPS status indicates HIGH
The
ONLINE
ALERT. The UPM status indicates ONLINE. The power module is on.
UPS OPERATING INSTRUCTIONS
pushbutton on the main menu bar. The System
command.
BYPASS
GO TO BYPASS
pushbutton on the main menu bar. The System
command.
UPS
GO TO HIGH ALERT
S
164201701 Rev 3 www.eaton.com/powerquality
.
.
7-35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power xpert 9395

Table of Contents