Transfer from High Alert to Online Mode

To transfer the critical load to Online mode:
NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer
Service Engineer.
1.
2.
3.
4.
5.
7.3.11

Transfer from Bypass to Energy Saver Mode

To transfer the critical load to Energy Saver mode:
NOTE The Energy Saver mode commands are displayed only if enabled at the factory or by an Eaton
Customer Service Engineer.
1.
2.
3.
4.
5.
t
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
Press the
pushbutton on the UPS Command menu bar.
SELECT
The UPS transfers to High Alert mode, but remains Online. After one hour the
UPS transfers to Energy Saver mode and the critical load is immediately supplied
by the bypass source. If the bypass source is not available, the power module
remains on and an alarm sounds.
status indicator is illuminated. The UPS status indicates HIGH
The
ONLINE
ALERT. The UPM status indicates ONLINE. The power module is on.
Press the
pushbutton on the main menu bar. The System Status
CONTROLS
screen is displayed.
On the System Status screen, select the
Press the
pushbutton on the System Status menu bar. The UPS
CONTROLS
Control Command screen is displayed.
On the UPS Control Command screen, select
Press the
pushbutton on the UPS Command menu bar.
SELECT
The UPS transfers to Online mode.
status indicator is illuminated. The UPS status indicates ONLINE. The
The
ONLINE
UPM status indicates ONLINE.
Press the
pushbutton on the main menu bar. The System Status
CONTROLS
screen is displayed.
On the System Status screen, select the
Press the
pushbutton on the System Status menu bar. The Bypass
CONTROLS
Control Command screen is displayed.
On the Bypass Control Command screen, select
Press the
pushbutton on the Bypass Command menu bar.
SELECT
The UPS transfers to Online mode and then to Energy Saver mode. The critical
load is supplied by the bypass source.
status indicator is illuminated. The UPS status indicates ENERGY
The
ONLINE
SAVER. The Bypass status indicates ON. The UPM status indicates ONLINE. If
the battery is not charging, the power module is off.
UPS OPERATING INSTRUCTIONS
command.
UPS
GO TO ONLINE
command.
BYPASS
GO TO ENERGY SAVER
S
164201701 Rev 3 www.eaton.com/powerquality
.
.