Mini-Slot Interface Connections; Installing Signal Interface Connections In Parallel System; Table 4-2. Dry Contact Output Terminal - Eaton 93PR Series User And Installation Manual

Table of Contents

Advertisement

Table 4-2: dry Contact Output Terminal
User logical selection
NO
NC
4.4.4

Mini-slot Interface Connections

For Mini-slot accessories and communication devices selection see Chapter 5 Communication interfaces. For
installation and setup of a Mini-slot card, please contact your Eaton representative.
To install wiring to connections:
1. If not already installed, install the LAN and telephone drops.
2. Open the front door of the UPS.
3. Remove the particular Mini-slot cover plate by removing the two screws securing the plate and install the
device by pushing it all the way in.
4. Secure the Mini-slot communication device with two screws.
5. Route and install the LAN, telephone, and other cables to the appropriate Mini-slot cards. Cable route is
through the signal cable canal, on top section of the UPS.
6. Refer to the manual supplied with the Mini-slot card for operator instructions.
7 . When all wiring is completed, close the front door and secure the latch.
4.4.5

Installing Signal Interface Connections In Parallel System

Installation of signal interface connections in parallel system is done by following the aforementioned
instructions. Signal inputs can be paralleled between the units, that is, the same contact can be used for
several units' signal input signaling. This concerns also the EPO-signal.
Terminal pins connection
shows on HMI
2-3
1-3
25-75 kW
User's and Installation Guide
Note
Pin1 disconnection
Pin2 disconnection
44

Advertisement

Table of Contents
loading

This manual is also suitable for:

93pr 50(75)93pr 75(75)93pr 25(75)