Using The Lcd And Pushbuttons; Figure 7‐3. Parts Of The Lcd - Eaton Power Xpert Plus 1 Installation And Operation Manual

450–550 kva
Table of Contents

Advertisement

UPS OPERATING INSTRUCTIONS
A
ALARM:
INPUT
B
BATT
BYPASS
C
EVENTS
D
A
The UPS status area automatically scrolls between the Eaton model number, current date and time, active
alarms, active notices, and load percent and battery runtime for the UPS. If the Environmental Monitoring
Probe is installed, the temperature and humidity sensed by the probe will also be displayed. The top line of
display blinks while scrolling when the system needs attention. Some notices and alarms may be accompanied
by an audible horn. To silence the horn, press any control panel pushbutton once
message. For more information about alarms and notices, see paragraph 7.2.2.
B
The information area contains data about UPS status and operations.
C
The menu bar lists the titles of the available screens. To select a screen, press the pushbutton underneath the
desired screen.
D
The navigation pushbuttons function depending on the screen displayed. Use the pushbuttons to select menu
screens or scroll through available screens. The LCD options above the pushbuttons indicate each
pushbutton's function.
t
7-4
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
7.2.3

Using the LCD and Pushbuttons

The LCD on the control panel provides an operator interface with the UPS system.
Figure 7‐3 identifies the display areas discussed in the following sections.
INPUT AC UNDER VOLTAGE
UPS
METERS
Figure 7‐3. Parts of the LCD
You can use the LCD and the pushbuttons to:
S
Look at a log of UPS events (alarms, notices, and commands) (see paragraph 7.2.6)
S
Monitor UPS operation (see paragraph 7.2.6)
S
Set UPS parameters (see paragraph 7.2.6)
S
Control UPS operation (see paragraphs 7.2.7 and 7.2.8)
After approximately 30 minutes, the display screen darkens. To restore the screen,
press any pushbutton once.
STSW
SETUP
CONTROLS
S
164201701 Rev 3 www.eaton.com/powerquality
OUTPUT
LOAD OFF
Shown is a typical alarm
.