7.3.10
Disable Energy Saver System Mode from the Bypass Command
Menu
To disable Energy Saver System mode:
NOTE The Energy Saver System mode commands are displayed only if enabled at the factory or by an
Eaton Customer Service Engineer.
NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
If the Variable Module Management System mode is enabled, the Energy Saver System mode commands will
not be displayed.
1.
Press the
CONTROLS
screen is displayed.
2.
On the System Status screen, select the
3.
Press the
CONTROLS
Control Command screen is displayed.
4.
On the Bypass Control Command screen, select
5.
Press the
SELECT
If the UPS is online, the UPS transfers to Battery mode and then to Online mode.
The Online status indicator is illuminated. The UPS status indicates ONLINE. The
UPM status indicates ONLINE.
7.3.11
Start Energy Saver System High Alert Mode from the Bypass
Command Menu
To start High Alert mode:
NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer
Service Engineer.
NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
If the Variable Module Management System mode is enabled, the Energy Saver System mode commands will
not be displayed.
1.
Press the
CONTROLS
screen is displayed.
2.
On the System Status screen, select the
3.
Press the
CONTROLS
Control Command screen is displayed.
4.
On the Bypass Control Command screen, select
5.
Press the
SELECT
If the UPS is online, the UPS starts High Alert mode with the UPMs online
supplying the critical load. After one hour the UPS transfers to Energy Saver
System mode.
The Online status indicator is illuminated. The UPS status indicates HIGH
ALERT. The UPM status indicates ONLINE. The power module is on.
pushbutton on the main menu bar. The System Status
BYPASS
pushbutton on the System Status menu bar. The Bypass
pushbutton on the Bypass Command menu bar.
pushbutton on the main menu bar. The System Status
BYPASS
pushbutton on the System Status menu bar. The Bypass
pushbutton on the Bypass Command menu bar.
S
164201716 Rev 2 www.eaton.com/powerquality
command.
.
DISABLE ENERGY SAVER
command.
.
START HIGH ALERT