Start Energy Saver High Alert Mode from the Bypass
Command Menu
To start High Alert mode:
NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer
Service Engineer.
NOTE Advanced Power Management and Energy Saver modes are mutually exclusive. If Advanced Power
Management is enabled, Energy Saver commands will not be displayed.
1.
Press the
CONTROLS
screen is displayed.
2.
On the System Status screen, select the
3.
Press the
CONTROLS
Control Command screen is displayed.
4.
On the Bypass Control Command screen, select
5.
Press the
SELECT
If the UPS is online, the UPS starts High Alert mode with the UPMs online
supplying the critical load. After one hour the UPS transfers to Energy Saver
mode.
status indicator is illuminated. The UPS status indicates HIGH
The
ONLINE
ALERT. The UPM status indicates ONLINE. The power module is on.
7.3.12
Enable Advanced Power Management Mode from the Bypass
Command Menu
To enable Advanced Power Management mode:
NOTE The Advanced Power Management mode commands are displayed only if enabled at the factory or
by an Eaton Customer Service Engineer.
NOTE Advanced Power Management and Energy Saver modes are mutually exclusive. If Energy Saver is
enabled, Advanced Power Management commands will not be displayed.
1.
Press the
CONTROLS
screen is displayed.
2.
On the System Status screen, select the
3.
Press the
CONTROLS
Control Command screen is displayed.
4.
On the Bypass Control Command screen, select
MANAGEMENT
5.
Press the
SELECT
If the UPS is online, the UPS transfers to Advanced Power Management mode.
In approximately twenty seconds the UPS calculates the required number of
UPMs needed to support the load.
status indicator is illuminated. The UPS status indicates ONLINE +
The
ONLINE
APM. The UPM status indicates ONLINE.
t
9395 UPS (1000–1100 kVA) Installation and Operation Manual
pushbutton on the main menu bar. The System Status
pushbutton on the System Status menu bar. The Bypass
pushbutton on the Bypass Command menu bar.
pushbutton on the main menu bar. The System Status
pushbutton on the System Status menu bar. The Bypass
.
pushbutton on the Bypass Command menu bar.
S
164201764 Rev 3 www.eaton.com/powerquality
command.
BYPASS
.
START HIGH ALERT
command.
BYPASS
ENABLE ADV POWER