7.3.11
7.3.12
t
Power Xpert
9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual
4.
On the Bypass Control Command screen, select
5.
Press the
pushbutton on the Bypass Command menu bar.
SELECT
If the UPS is online, the UPS transfers to Battery mode and then to Online mode.
The Online status indicator is illuminated. The UPS status indicates ONLINE. The
UPM status indicates ONLINE.
Start Energy Saver System High Alert Mode from the Bypass
Command Menu
To start High Alert mode:
NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer
Service Engineer.
NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
If the Variable Module Management System mode is enabled, the Energy Saver System mode commands will
not be displayed.
1.
Press the
pushbutton on the main menu bar. The System Status
CONTROLS
screen is displayed.
2.
On the System Status screen, select the
3.
Press the
pushbutton on the System Status menu bar. The Bypass
CONTROLS
Control Command screen is displayed.
4.
On the Bypass Control Command screen, select
5.
Press the
pushbutton on the Bypass Command menu bar.
SELECT
If the UPS is online, the UPS starts High Alert mode with the UPMs online
supplying the critical load. After one hour the UPS transfers to Energy Saver
System mode.
The Online status indicator is illuminated. The UPS status indicates HIGH
ALERT. The UPM status indicates ONLINE. The power module is on.
Enable Variable Module Management System Mode from the Bypass
Command Menu
To enable Variable Module Management System mode:
NOTE The Variable Module Management System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
If the Energy Saver System mode is enabled, the Variable Module Management System mode commands will
not be displayed.
1.
Press the
pushbutton on the main menu bar. The System Status
CONTROLS
screen is displayed.
2.
On the System Status screen, select the
3.
Press the
pushbutton on the System Status menu bar. The Bypass
CONTROLS
Control Command screen is displayed.
UPS OPERATING INSTRUCTIONS
DISABLE ENERGY SAVER
command.
BYPASS
START HIGH ALERT
command.
BYPASS
S
www.eaton.com/powerquality
164201710 Rev 7
.
.
7-19