Table 4 Temperature And Humidity Requirements - Zte ZXR10 8900 Series Hardware Installation Manual

Zxr10 8900 series 10 gigabit routing switch
Hide thumbs Also See for ZXR10 8900 Series:
Table of Contents

Advertisement

ZXR10 8900 Series Hardware Installation Manual
12
Confidential and Proprietary Information of ZTE CORPORATION
T
4 T
ABLE
EMPERATURE AND
Temperature
Items
Long-term
working
condition
Range
15°C
~30°C
Note:
When equipment is in normal running environment, tem-
perature and humidity measurement points refer to values
measured at points 2m above floor and 0.4m in front of
equipment (they must be measured when there is no pro-
tection plate in front and back of cabinet.
Short-term working condition: Do work continuously but
not more than 48 hours, or the work time is not more than
15 days every year.
Air conditioner is recommended to use.
Prepare two AC power supply or dynamotor to guaran-
tee air conditioner run properly.
Prepare central air conditioner or more than two small
air conditioners in NOC room to guarantee appropriate
temperature.
Lighting
Measures must be taken against direct sunshine, thus to avoid
aging and deformation of elements like circuit boards.
Average luminance must be 150lx~200lx. Generally, fluores-
cent lamps embedded into the ceiling are adopted.
An emergency illumination lamp (DC lamp) can be mounted
for buildings with frequent power failure. Battery room must
be equipped with anti-explosion lamps and the light needs not
to be too intense.
In addition, direct sunshine must be avoided. To this aim, pa-
per or paint can be used on external window.
Atmospheric pressure
Working: 108000Pa~51000Pa
Storage: 108000Pa~12000Pa
Air Pollution
The product must not be exposed in corrosive gases such as
sulfured hydrogen, sulfur dioxide and ammonia oxide, and
smog such as oil fluxing agent and smoke dust. Smoking must
be prohibited near battery. In addition, this is recommended
to prohibit smoking in all areas where equipment is placed.
Fireproof
H
R
UMIDITY
EQUIREMENTS
Relative Humidity
Long-term
Short-term
working
working
conditions
condition
-5°C
40%~65%
~45°C
Short-term
working
conditions
20%~90%

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zxr10 8912Zxr10 8908Zxr10 8905Zxr10 8902

Table of Contents