P110 Level Source [6 relay model]
Sets the level source on which the indexed relay is assigned to a measurement point.
Please note that Difference and Average settings are features of the HydroRanger 200
6 relay model.
Primary Index
Values
Altered by:

HydroRanger 200 [6 relay model]

Please note that these features are only available on the HydroRanger 200 6 relay model.
In Single Point Mode (standard):
Points 2 and 3 are available only if Operation is set for difference or average
(P001 = 4 or 5).
In Dual Point Mode (optional):
Point 2 is always available, and Point 3 is available only if Operation is set for difference or
average (P001 = 4 or 5).
P111 Relay Control Function
Sets the control algorithm used to trip the relay.
Please note that parameter P111 values vary between the HydroRanger 200, 1 or 3 relay
model and the HydroRanger 200, 6 relay model.
Primary Index
Values
Altered by
Use zero 0 (preset) to disable control of the indexed relay.
All relay ON/OFF points must be referenced from Empty (P006), regardless
Note:
of Operation Mode selection (POO1).
7ML19985FC03
Relay
Range: 1 to 3
1
* Point # 1 = Transducer One
2
Point # 2 = Transducer Two
3
Point # 3 = Difference (P001=4) or Average (P001=5)
[6 relay
[6 relay model]
model]
P003 Maximum Process Speed
P700 Max Fill rate
P701 Max Empty rate
P070 Failsafe Timer
P071 Failsafe Material Level
Relay
See chart below
P100 Preset Applications
HydroRanger 200 – INSTRUCTION MANUAL