P171 Flush Cycles [6 relay model]
Sets the number of pump cycles requiring flush control.
Primary Index
Values
Related
If three flush cycles are required after every ten pump cycles then:
P172 (Flush Interval) = 10
P171 (Flush Cycles) = 3
P172 Flush Interval [6 relay model]
Sets the number of pump cycles before flush control is enabled.
Primary Index
Values
Related
To start a new flush cycle every ten times the pumps are run, set this to 10.
P173 Flush Duration [6 relay model]
The length of time for each flush cycle that the flush control is active.
Primary Index
Values
Related
Page 144
Single Point Model
Global
Range: 0 to 9999
Preset: 0
P111 = 64, Flush Valve
Single Point Model
Global
Range: 0 to 9999
Preset: 0
P111 = 64, Flush Valve
Single Point Model
Global
Range: 0.000 to 9999 s
Preset: 0.000
P111 = 64, Flush Valve
HydroRanger 200 – INSTRUCTION MANUAL
Dual Point Model
Relay
Dual Point Model
Relay
Dual Point Model
Relay
7ML19985FC03