Siemens HMS-2S Installation Instructions

Advertisement

Quick Links

Installation Instructions
Models HMS-2S / HMS-SA
Dual Stage Manual Pull Station (For Canadian Two-Stage Applications)
Single Stage Manual Pull Station with Auxiliary Contacts
INTRODUCTION
PROGRAMMING
INSTRUCTIONS
OPERATION
P/N 315-033430-6
The Model HMS-2S/-SA Manual Station from Siemens
Industry, Inc., is a field installed addressable device
containing advanced control panel communication
technology. This technology, which provides two-
direction communication with the control panel,
produces an Intelligent Initiating Device.
Refer to Figure 1 to locate the opening on the HMS cover that allows access to the
programming holes which are on the HMS printed
circuit board.
To connect the HMS to the DPU Programmer/Tester,
insert the plug from the DPU cable provided with the
Programmer/Tester into the opening on the HMS as
shown in Figure 2. Because HMS devices are polarity
insensitive, the programming plug can be inserted into
the programming holes in either direction.
To prevent potential damage to the DPU DO NOT
connect an HMS to the DPU until at least one wire is
removed from terminals 1 or 2 of the HMS.
Follow the instructions in the DPU Manual (P/N 315-033260) to program the HMS to
the desired address. Record the device address on the label located on the HMS
front panel. The HMS can now be installed and wired to the system.
The HMS manual station operates with the FireFinder-XLS Control Panel via the DLC
Device Loop Card.
The HMS-2S/-SA manual station housing has a pull down lever that locks in position
after releasing a spring loaded switch. (See Figure 4.) To indicate the manual station is
activated, the pull down lever remains down and locked until the station is physically
reset. The HMS-2S/-SA manual station has a set of normally closed auxiliary contacts
which are available for releasing door holders and magnetic door locks.
The HMS-2S has a keyswitch which can activate a second address.
The unit is reset by opening the hinged housing cover with an Allen key and then
closing and locking the cover, or by returning the keyswitch to its original position.
Figure 1
HMS Cover
PROGRAMMING
POINTS
LOCATING TAB
Figure 2
Connecting the DPU Plug
Siemens Industry, Inc.
Building Technologies Division
OPENING TO
PROGRAMMING
POINTS
PLUG FROM
DPU

Advertisement

loading

Summary of Contents for Siemens HMS-2S

  • Page 1 The HMS manual station operates with the FireFinder-XLS Control Panel via the DLC Device Loop Card. The HMS-2S/-SA manual station housing has a pull down lever that locks in position after releasing a spring loaded switch. (See Figure 4.) To indicate the manual station is activated, the pull down lever remains down and locked until the station is physically reset.
  • Page 2 Current maximum: 1mA In supervisory: HMS-2S / HMS-SA draws 1mA. Figure 3 8. The HMS-2S / HMS-SA is a polarity insensitive device. Line 1 and Line 2 HMS-2S / HMS-SA Wiring Information can be either line of the loop. The use of limited energy cable is not allowed.

This manual is also suitable for:

Hms-sa