P620 Low Flow Cutoff [6 relay model]
Eliminates totalizer activity for flows at or below the cutoff value.
Primary Index
Values
Altered By
Related
Use this to enter the minimum head in units (P005) or as a percent of span.
P621 Auto Zero Head [6 relay model]
Calibrates Zero Head (P605) based on actual head measurements.
Primary Index
Values
Related
Use this parameter when the reported head is consistently high or low by a fixed amount.
Before using this feature, verify the following parameters are correct:
Empty (P006)
Temperature (P664)
Offset Reading (P062=0)
Zero Head Offset (P605)
Procedure, with "head" steady
1.
Press TRANSDUCER
2.
Repeat step ONE at least FIVE times to verify repeatability.
3.
Measure the actual head (with a tape measure or solid rule).
4.
Enter the actual head value.
The deviation between the entered Empty (P006) value and the calibrated Empty value is
stored in Offset Correction (P652). Alternatively, the Empty parameter (P006) can be
corrected directly.
7ML19985FC03
Single Point Model
Global
Range: 0.000 to 9999
Preset = 5.000 %, or equivalent units
P005 Units
P007 Span
Single Point Model
Global
Range: -999 to 9999
P006 Empty
P062 Offset Reading
P605 Zero Head
P664 Temperature
to display the calculated head.