Please note the following:
enter value in current units (as selected in P005)
valid for level, space, and distance
volume is calculated based on the Backup level
Example:
Transducer One is configured for a level measurement. Digital Input 2 is connected to a Hi
Level Backup switch located a level of 4.3m.
Parameter
P064
P065
When the level rises to 4.3m, and the switch is activated, the reading is forced to 4.3m.
The reading stays at 4.3m until the switch is de-activated.
P066 Override Time Delay
Defines the time used to calm (debounce) the override condition input. Set in seconds.
Primary Index
Values
Related
Note: Activation of the Level Override is subject to the measurement cycle. This
can add up to four seconds to the overall response time depending on operating
conditions and programming.
P069 Password
Holds the current password for P000. Select by typing in 069. You cannot scroll to this
parameter.
Primary Index
Values
Related
This parameter is write-only, and can only be selected by entering 069. To change the
password, unlock the device by entering the current password into P000. Then enter the
new password into P069. To lock the device, enter a password other than the correct one
in P000. While the device is unlocked, the password is visible in P000.
7ML19985FC03
Index
1
1
Transducer
Range: 0.0 to 9999
Preset: 5.0
P064 Override Enable
P065 Reading Override Value
P270 Discrete Input Function
Global
Range: 0 to 9999
Default: 1954
P000 Lock
HydroRanger 200 – INSTRUCTION MANUAL
Value
2
4.3
Page 129