Universal, Linear [6 Relay Model]; Universal, Curved [6 Relay Model] - Siemens HydroRanger 200 Instruction Manual

Table of Contents

Advertisement

Universal, Linear [6 relay model]

Please note that the Universal, Linear feature is only available on the HydroRanger 200,
6 relay model.
Set P600 = 4.
This flow calculation creates a piece-wise linear approximation of the head/flow curve.
This option provides best results if the curve has sharp angles joining relatively linear
sections.
Enter a Head Breakpoint at each point where the head/flow curve bends sharply (2
minimum). For combination curves (mostly linear but include 1 or more arcs), enter
numerous breakpoints along the arc, for best flow calculation accuracy.
Typical Flow Characterization
See also

Universal, Curved [6 relay model]

Please note that the Universal, Curved feature is only available on the HydroRanger 200,
6 relay model.
This calculation creates a cubic spline approximation of the head/flow curve, providing
best results if the curve is non-linear, and there are no sharp angles.
Select at least enough breakpoints from the curve to satisfy the following:
two breakpoints very near the minimum head
one breakpoint at the tangent points of each arc
one breakpoint at each arc apex
two breakpoints very near the maximum head
7ML19985FC03
HydroRanger 200 – INSTRUCTION MANUAL
on page 81.