P803 Shot / Pulse Mode
Determines what type of ultrasonic shots are fired.
Primary Index
Values
Related
Increases HydroRanger 200 response when the monitored surface is close to the
transducer face. Select short and long to have short and long acoustic shots fired for
each measurement, regardless of the transducer to surface distance. Select short to
have only short shots fired if the Echo Confidence (P805) produced by a short shot
exceeds the short Confidence Threshold (P804) and the monitored surface is always
within the Short Shot Range (P852).
P804 Confidence Threshold
Determines which echoes are evaluated by software.
Primary Index
Values
Related
The short and long shot Confidence Thresholds are preset to 10 and 5 respectively. When
Echo Confidence (P805) exceeds the Confidence Threshold, the echo is evaluated by
Sonic Intelligence®. Values are entered as two numbers separated by a decimal point.
The first number is the short shot confidence and the second number is the long shot
confidence.
The decimal point is replaced with a colon (:) on the display.
Note:
7ML19985FC03
Single Point Model
Global
1
Short
2
*
Short and long
P006 Empty
P805 Echo Confidence
P804 Confidence Threshold
P852 Short Shot Range
Single Point Model
Global
Range: 0 to 99:0 to 99
Preset: 10:5
P805 Echo Confidence
HydroRanger 200 – INSTRUCTION MANUAL