Pump Setpoint Modifiers (P121 And P122) [6 Relay Model] - Siemens HydroRanger 200 Instruction Manual

Table of Contents

Advertisement

Positive Logic
In software, all relays are programmed the same way, with ON setpoints indicating when
to change the relay contact state (open or closed). This parameter allows the reversal of
the operation so that relay contacts can be NORMALLY CLOSED or NORMALLY OPEN.
P118 is preset to 2 which is positive logic.
Negative Logic
When P118 = 3 (negative logic), the operation for the indexed relay is reversed from
normal.
P119 Relay Logic Test
Forces the relay control logic into an ACTIVATED or DE-ACTIVATED state.
Primary Index
Values
Related
This parameter tests site wiring and control logic programming. Forcing the relay to an
activated or de-activated state is similar to the HydroRanger 200 detecting an event and
responding to it. Helpful in testing new installations and diagnosing control problems.
Pump Setpoint Modifiers (P121 and P122)
[6 relay model]
Please note that these parameters apply to the HydroRanger 200 6 relay model only.
These parameters provide alternate ways of starting the pumps in the pump group. See
Pump Control
the
P121 Pump by Rate [6 relay model]
Sets the pump relays to accept control by rate of level change once the first ON setpoint
is reached.
Primary Index
Values
Related
Page 138
Relay
0
*
OFF - Control from HydroRanger 200 algorithms
1
Activate relay control
2
De-activate relay control
P111 Relay Control Function
P910 Toggle Relays
section on page 56 for descriptions of the pump control algorithms.
Single Point Model
Transducer
0
*
OFF (pump by level)
1
ON (pump by rate)
P007 Span
P111 Relay Control Function
P132 Pump Start Delay
Rate (P700 to P708)
HydroRanger 200 – INSTRUCTION MANUAL
Dual Point Model
Level
7ML19985FC03