P664 Temperature
View the transducer temperature in °C.
Primary Index
Values
Altered By
Related
Value is displayed when
page 22).
If Temp Source (P660) is set to any value other than Fixed Temp, the value displayed is the
temperature measured. If Temp Source is set to Fixed Temp, the P661 value is displayed.

Rate (P700 to P708)

These parameters determine how material level changes are reported.
P700 Max Fill Rate
Adjusts the HydroRanger 200 response to increases in the actual material level (or
advance to a higher Failsafe Material Level, P071).
Primary Index
Values
Altered by
Related
Enter a value slightly greater than the maximum vessel filling rate. This value, in Units
(P005) or % of Span (P007) per minute, is automatically altered when Maximum Process
Speed (P003) is altered.
P003 Value
1
2
3
7ML19985FC03
Transducer
Range: -50 to 150 (view only)
P660 Temp Source
P651 Sound Velocity Calibration
P653 Velocity
P654 Velocity at 20°C
P661 Temp Fixed
is pressed in RUN mode (see
Single Point Model
Global
Range: 0.000 to 99.00 m (or equivalent depending on units)
P003 Maximum Process Speed
P005 Units
P007 Span
P071 Failsafe Material Level
HydroRanger 200 – INSTRUCTION MANUAL
Readings in Run Mode
Dual Point Model
Transducer
Meters/Minute
0.1
1
10
on
Page 183