Chapter 12. CALIBRATION
Writing into EEPROM
Carbon potential code calibration
Carbon potential code calibration
Writing into EEPROM
12-16
(1) Press SETUP key until the PROG/SEG display shows (06-09).
Scroll ↑, ↓, ←, →, keys to show (1.1.1.1.) on upper display.
(2) Press ENTER key.
Scroll ↑, ↓, ←, →, keys to show (7.0.7.7.) on upper display, then press ENTER
key.
Press SETUP key until the PROG/SEG display shows (07-01).
Scroll ↑, ↓, ←, →, keys to show (x.x.x.x.) on upper display, then press ENTER
key (See Table 12-11).
(1) Press SETUP key until the PROG/SEG display shows (07-02).
Scroll ↑, ↓, ←, →, keys to show (1.1.1.1.) on upper display.
(2) Press ENTER key.
Table 12-11. Carbon Potential Code
Upper Display
0.0.0.0.
DCP552 standard model
DCP552 carbon potential for PV ch 2
0.0.0.1.
Function