DCP552 Parameter Work Sheet
User name
Equipment name
Model No.
Instrumentation staffer in charge :
Variable parameter setting
No. Item code
1
Key lock
PA 01
2
Memory protect
PA 02
3
Display channel setting
PA 03
4
Synchronous 2 channel
PA 04
operation
5
Program auto load
PA 05
8
Auto-tuning (CH1)
PA 08
9
PA 09
Auto-tuning MV lower limit (CH1)
10 PA 10
Auto-tuning MV higher limit (CH1) 100.0
11 PA 11
SP bias (CH1)
12 PA 12
PV digital filter (CH1)
13 PA 13
PV bias (CH1)
14 PA 14
Manipulated variable deviation 110.0
limit (CH1)
15 PA 15
Time proportional output cycle (CH1) 10
16 PA 16
On-off control differential (CH1) 50 SPU
17 PA 17
PID computation initialize
manipulated variable (CH1)
21 PA 21
SP bias (CH2)
22 PA 22
PV digital filter (CH2)
23 PA 23
PV bias (CH2)
24 PA 24
Manipulated variable
deviation limit (CH2)
25 PA 25
Time proportional output
cycle (CH2)
26 PA 26
ON-OFF control differential
(CH2)
27 PA 27
PID computation initialize
manipulated variable (CH2)
31 PA 31
Group 1 event number
32 PA 32
Group 1 delay time
33 PA 33
Group 2 event number
34 PA 34
Group 2 delay time
35 PA 35
Group 3 event number
:
:
:DCP552
Item
Factory default User
settings
0
0
0
0
0
0
0.0
0 SPU
0.0
0 PVU
0.0
0
0.0
0 PVU
110.0
10
50
0.0
0
0.0
0
0.0
0
Preparation date
Product name
Tag name
Business staffer in charge :
Settings and descriptions
settings
0 : Keylock disabled
1 : Display of setup data settings disabled
2 : Display of all settings disabled
3 : Display of all settings disabled. Operation keys disabled.
0 : Disabled
1 : Program settings are protected.
2 : Setup, variable parameters and event configuration
settings are protected.
3 : Setup, variable parameters, event configurations
and program settings are protected.
4 : Setup, variable parameters, event configurations
and PID parameter settings are protected.
5 : Program settings and all parameter settings are protected.
0 : 2 items are displayed for the selected CH
1 : Simultaneous 2CH display of the same item
0 : asynchronous
1 : synchronous
0 : OFF
1 : ON
0 : AT not performed
1 : Standard AT performed on currently used PID group
in mode other than READY mode
2 : AT writing overshoot-proof PID values to currently used
PID groups in mode other than READY mode performed
3 : Standard AT performed on PID groups A1 to A7 in
READY mode
4 : AT writing overshoot-proof PID values to PID groups
A1 to A7 in READY mode continuously performed
–5.0 to upper limit %
Lower limit to +105%
–10000 to +10000 SPU (CH1)
0.0 to 120.0sec
–1000 to +1000 PVU(PV1)
0.1 to 110.0% OUT / 0.1sec
1 to 240sec
0 to 1000 SPUm (CH1)
–5.0 to +105.0%
-10000 to +10000 SPU (CH2)
0.0 to 120.0sec
–1000 to +1000 PVU(PV2)
0.1 to 110.0% OUT/0.1 sec
1 to 240sec
0 to 1000 SPU (CH2)
-5.0 to +105.0%
0 to 16
(0: No delay is specified.)
0.0 to 3000.0sec
0 to 16
(0: No delay is specified.)
0.0 to 3000.0sec
0 to 16
(0: No delay is specified.)
:
:
:
1