Setting Event Items - Honeywell DCP552 Mark II User Manual

Digital control programmer
Table of Contents

Advertisement

Setting event items

Handling Precautions
When the event is a PV event
Display (PV events)
NOTE
Events assigned to the selected channel can be displayed.
Note that when setup data C57 is set to 1, event items on the programming
map are skipped and not displayed.
(1) In the set value display state, move to the segement event item to be set on the
programming map.
(2) Press the ENTER key to make display panel 1 flash (registration of first
setting).
(3) Use the ↑, ↓, ←, and → keys to make the first setting – setting the event
operating point.
Setting range : OFF –19999 to +20000 SPU
: OFF 0 to 20000 SPU (for absolute value deviation events)
: OFF –5.0 to +105.0% (for MV events)
(4) Press the ENTER key to stop the flashing on display panel 1. (Pressing the
FUNC and CLR keys causes display panel 1 to return to unset state "-----"
and the flashing stops.)
Set operating point
Event number
Event type
Unset values are indicated as " ----- ".
A PV event setting consists of a setting (including OFF) and a subfunction. A
subfunction cannot be used when a setting has not been made " ----- ".
Chapter 8. PROGRAM SETUP
PROG
SEG
Program
Segment
number
number
PROFILE
Pattern trend
8-7