Honeywell DCP552 Mark II User Manual page 48

Digital control programmer
Table of Contents

Advertisement

Chapter 5. FUNCTIONS
5 - 2
Pattern
RAMP-X system
5-2
Program Pattern
Separate programs are set in CH1 and CH2 for each program number.
Three systems for selecting programs are provided: RAMP-X, RAMP-T and
RAMP-E. The first segment of each program is always RAMP-X, but the other
segments can be any system and all three types can be used in one program.
This system, sets a segment of a pattern using SP and time, is called RAMP-X.
SP setting
: within the upper and lower SP limiter range
Time setting : 0 hours 00 minutes to 500 hours 00 minutes
0 minutes 00 seconds to 500 minutes 00 seconds or
0.0 seconds to 3000.0 seconds
(Time units are selected using the C62 setup data setting.)
SP is a point on the elapsed time axis in the current segment, which is a straight
line connecting the start point, the SP set value in the previous segment, and the
end point, the SP set value in the current segment. Segments are classified as
follows.
•Rising RAMP (or rising slope)
Previous segment SP setting < current segment SP setting
•Falling RAMP (or descending slope)
Previous segment SP setting > current segment SP setting
•SOAK (soaking)
Previous segment SP setting = current segment SP setting
The start and end points of the first segment are also the SOAK segment of the SP
set value for the first segment.
SP calculation (other than first segment)
SP = (current segment SP set value – previous segment SP set value)
× (current segment elapsed time ÷ current segment time setting)
+ previous segment SP setting.
SP
SP set value of
previous segment
Time setting of current segment
SP set value of
current segment
Time

Advertisement

Table of Contents
loading

Table of Contents